Feature Article Archive

Electrical Safety - Understanding Grounding as a Fire Safety Necessity
Grounding Electrodes and Grounding Electrode Systems
Grounding and Bonding Basics
Multiwire Branch Circuits
Wiring Methods - Key Requirements
The Importance of Article 300
Navigating Chapter 3
Luminaires and Lighting Systems
Limited Energy Requirements
Electric Fire Pumps
Fire Pump Circuits
Making the Right Connection
Swimming Pool Wiring

 

Limited Energy Requirements in the NEC®

 

Mark W. Earley

 

Articles 725, 760, 770, 800, 820, and 830 are the articles of the NEC that cover limited energy systems. In the limited energy systems discussed in these articles, there is less concern that an electrical fault will cause a fire than there is with power distribution circuits. For many of these circuits, there is also less of a concern for shock hazards. The primary concerns for these articles include fire propagation along combustible insulation and through fire-rated assemblies and a concern about limited energy circuits being mingled with power circuits.

Many of the circuits discussed in these articles are control, signaling, alarm, or communications circuits. The number of these types of circuits is increasing in all types of facilities. As the number of circuits increase, the potential hazards also increase.

 

Cable Insulation

Two landmark fires in 1975 illustrated the problems that can exist if combustible insulation is used on cables. The first of the fires occurred in a telephone exchange in Manhattan. The fire started in the sub-basement cable vault of the 12-story exchange building and traveled vertically from floor to floor through unsealed floor penetrations. This fire affected several floors of the building and caused $90 million (1975 dollars) in damage. The fire injured over 100 fire fighters, and the resulting service interruptions affected approximately 200,000 customers. The second fire occurred a few weeks later at the Browns Ferry Nuclear Plant in Alabama. Cables penetrated fire walls that were sealed with combustible foam insulation. Workers were using candles to check the integrity of the foam seals (leaks in the foam seal would cause deflection of the flame). A candle ignited the fire which then spread into adjoining areas. The resulting blaze burned for nearly 8 hours, destroying over 1600 cables.

Although neither of these facilities was required to be built to NEC standards, these fires have had an impact on requirements in the NEC. Cables are now required to meet fire test standards, based on whether they will be installed as general wiring in a building, installed in a riser, or installed in a plenum. Openings around electrical penetrations through fire resistance–rated walls, partitions, floors, or ceilings are required to be firestopped using approved methods to maintain the fire resistance rating. These approved methods preclude the use of combustible material.

 

Abandoned Cables

Each of the limited energy articles requires the removal of the accessible portion of abandoned cables. Abandoned cables increase combustible loading and can create installation and maintenance problems. Excess accumulations of abandoned cables in plenums can obstruct the flow of environmental air.

 

Separation of Conductors

Class 1 circuits use 600-volt insulation. However, other limited energy circuits do not use 600-volt insulation. Therefore, separation of conductors is a concern that is addressed by requirements in each of the articles.

Computer local area network (LAN) circuits are considered to be Class 2 circuits and so must comply with Article 725. However, cables in computer rooms that meet the criteria of Section 645.4 do not need to meet the requirements of Article 725 if the installation meets the requirements of Article 645. Cables that leave the computer room must meet the requirements of Article 725. Article 645 installations are a unique and controlled environment. Most computer installations will not fall into the criteria of Article 645.

 

Structure and Numbering of Limited Energy Articles

The limited energy articles of the NEC contain some common themes. For this reason, the articles have been organized in a parallel numbering format.

 

 
 

                                        

 

Mark W. Earley, P.E., is Assistant Vice President of Electrical Engineering at NFPA, serves as secretary of the NEC® Committee, and is the chief editor of the National Electrical Code Handbook. He joined NFPA in 1986, is co-author of  Electrical Installations in Hazardous Locations, and has published numerous technical articles on the fire protection of electrical equipment.

                                       

Article 725 Class 1, Class 2, and Class 3 Remote-Control, Signaling, and Power-Limited Circuits

2008 NEC

 

2005 NEC 

I. General

725.1

Scope

725.1

725.2

Definitions

725.2

725.3

Other Articles

725.3

725.21

Access to Electrical Equipment Behind Panels Designed to Allow Access

725.7

725.24

Mechanical Execution of Work

725.8

725.25

Abandoned Cables – New Section

 

725.30

Class 1, Class 2, and Class 3 Circuit Identification

725.10

725.31

Safety-Control Equipment

725.11

725.35

Class 1, Class 2, and Class 3 Circuit Requirements

725.15

II. Class 1 Circuits

725.41

Class 1 Circuit Classifications and Power Source Requirements

725.21

725.43

Class 1 Circuit Overcurrent Protection

725.23

725.45

Class 1 Circuit Overcurrent Device Location

725.24

725.46

Class 1 Circuit Wiring Methods

725.25

725.48

Conductors of Different Circuits in the Same Cable, Cable Tray, Enclosure, or Raceway

725.26

725.49

Class 1 Circuit Conductors

725.27

725.51

Number of Conductors in Cable Trays and Raceway, and Derating

725.28

725.52

Circuits Extending Beyond One Building

725.29

III. Class 2 and Class 3 Circuits

725.121

Power Sources for Class 2 and Class 3 Circuits

725.41

725.124

Circuit Marking

725.42

725.127

Wiring Methods on Supply Side of the Class 2 or Class 3 Power Source

725.51

725.130

Wiring Methods and Materials on the Load Side of the Class 2 or Class 3 Power Source

725.52

725.133

Installation of Conductors and Equipment in Cables, Compartments, Cable Trays, Enclosures, Manholes, Outlet Boxes, Device Boxes, and Raceways for Class 2 and Class 3 Circuits

725.54

725.136

Separation from Electric Light, Power, Class 1, Non–Power-Limited Fire Alarm Circuit Conductors, and Medium-Power Network-Powered Broadband Communications Cables

725.55

725.139

Installation of Conductors of Different Circuits in the Same Cable, Enclosure, or Raceway

725.56

725.141

Installation of Circuit Conductors Extending Beyond One Building

725.57

725.143

Support of Conductors

725.58

725.154

Applications of Listed Class 2, Class 3, and PLTC Cables

725.61

IV. Listing Requirements

725.179

Listing and Marking of Class 2, Class 3, and Type PLTC Cables

725.82

 

 

Article 760 Fire Alarm Systems

2008 NEC

 

      2005 NEC

I. General

760.1

   Scope

      760.1

760.2

   Definitions

      760.2

760.3

   Other Articles

      760.3

760.24

   Mechanical Execution of Work

      760.8

760.9

   Fire Alarm Circuit and Equipment Grounding –Deleted Section

 

760.25

   Abandoned Cables – New Section

 

760.30

   Fire Alarm Circuit Identification

      760.10

760.32

   Fire Alarm Circuits Extending Beyond One Building

      760.11

760.35

   Fire Alarm Circuit Requirements

      760.15

II. Non–Power-Limited Fire Alarm (NPLFA) Circuits

760.41

   NPLFA Circuit Power Source Requirements

      760.21

760.43

   NPLFA Circuit Overcurrent Protection

      760.23

760.45

   NPLFA Circuit Overcurrent Device Location

      760.24

760.46

   NPLFA Circuit Wiring

      760.25

760.48

   Conductors of Different Circuits in the Same Cable, Enclosure, or Raceway

      760.26

760.49

   NPLFA Circuit Conductors

      760.27

760.51

   Number of Conductors in Cable Trays and Raceways, and Derating

      760.28

760.53

   Multiconductor NPLFA Cables

      760.30

III. Power-Limited Fire Alarm (PLFA) Circuits

760.121

   Power Sources for PLFA Circuits

      760.41

760.124